MIC 1166 1/16 DIN Microbased Profile Controller
  

MIC 1166 1/16 DIN Microbased Profile Controller

 RIM M100 Encoder Tester
 

Quick Specs...

  • Small Size - Maximum Function
  • Programmable profile device

  • Holds up to 4 programs of 16 free-format segments

  • Stores and implements temperature control sequences including ramp/soak profiles using exclusive PID techniques.

 






Buy Online

Printer-friendly Version

Dimensional Diagrams

Product Configurator

 

Overview Industry/Application Specifications Related Info  

Overview / Design Principle:

The Partlow brand MIC 1166 1/16 DIN profiler may seem small, but it packs a punch with holding up to 4 programs of 16 free-format segments each and includes an event output. The controller can be configured from the front of the instrument or by a PC through a configuration port. The configuration port has a dual purpose; first it can be used to modify the controller setups and secondly, it can be used to transfer programs or profiles.

This control has RaPID, Response Assisted PID, a fuzzy logic algorithm plus a pre-tune algorithm, that when combined provide shorter start-up times and reduced overshoot.

The Partlow brand MIC 1166 contains many of the features of larger more expensive profilers such as: guaranteed soak, delayed start, profile active output, profile recovery features, profile cycling, plus an optional digital input for remote run/hold. RS-485 communications is also available with convenient, full access to all profile data.

Modular I/O options allow for field upgrades by adding or replacing boards.

Features / Benefits:

  • Dual, 4-digit, LED displays
  • 1/16 DIN panel mount
  • Universal Input for thermocouple, RTD, DC linear mA/V/mV user-selectable
  • Up to 3 outputs; relay, 4-20mA, SSR driver, Triac
  • Alarm, control, retransmit, event output functions
  • PID, ON/OFF, profile (ramp/soak) control
  • Optional RS-485 serial communications
  • Program security

Applications:

Programmable profile device that stores and implements temperature control sequences including ramp/soak profiles using exclusive PID techniques.

Industries:

  • Industrial and lab ovens/furnaces, plastics and thermal forming
  • Form/fill and seal
  • Packaging applications
  • Semiconductor 
  • And any others where low costs, smaller size and unmatched connectivity are critical requirements.
Standard Features
  • Dual Display for fast view of process and control parameters
  • Full PID capability
  • Universal input for voltage, current, thermocouple and RTD
  • Profile Cycling
  • Program loading via communications port

Environmental Charateristics
Operating Temperature: 0 to 55°C, 32 to 131°F
Storage Temperature: -20 to 80°C, -4 to 176°F
Humidity: 20 to 95% RH, non condensing

Electrical
Line Voltage: 90 - 264VAC, 50/60 Hz
Power Consumption: 4 Watts
Common Mode Rej.: 120 db at 50/60 Hz
Series Mode Rej.: > 500% of span 50/60 Hz

Inputs
Thermocouple Types : J, K, T, R, S, B, L and N
RTD: Three-wire PT100, DIN 43760
Volts (VDC): 0-5, 1-5, 0-10, 2-10
Millivolts: 0 - 50 mVDC, 10 - 50 mVDC
Milliamps: 0 - 20 mA or 4 - 20 mA
Sample Rate: 250 ms

Outputs
Relay: SPDT rated at 2 amps resistive at 120/240 VAC
SSR Driver: > 4.3 VDC into 250Ω minimum
Triac Output: 1 amp @ 40°C derated to 1/2 amp @ 80°C
Current Output: 0 - 20 mA, 4 - 20 mA, eight bit resolution
Volts DC Output: 0 - 10 V, 0 - 5 V, eight bit resolution

Control
Control Types: RaPID, PID, PID/on-off, on-off
RaPID: Response Assisted PID is a fuzzy logic mixing / weighting of P, I, and D terms to provide dramatic performance improvements as compared to conventional PID techniques.
Auto Tune Types: Pre-Tune
Proportional Bands: 0 (OFF), 0.5% - 999.9% of input scan @ 0.1% increments
Auto Reset: 1s-99min 59sec and OFF
Rate: 0 (OFF) - 99min 59sec
Manual Reset: Adjustable in the range 0-100% of output power (single output) or -100% to +100% of output power (dual output)
Deadband / Overlap: -20% to +20% of proportional band 1 + proportional band 2
ON / OFF Hysteresis: 0.1% to 10.0% of input span
Auto / Manual Control: User-selectable with "bumpless" transfer into and out of Manual control.
Cycle Times: Selectable for 0.5sec to 512sec in binary steps
Setpoint Range: Limited by Setpoint Upper and Setpoint Lower Limits
Setpoint Ramp: Ramp rate selectable 1-9999 LSDs per hour and infinite. Number displayed is decimal point aligned with selected range.

Alarms
Maximum Number: Two "soft" alarms
Maximum # Outputs: Up to 2 outputs can be used for alarm purposes
Combination Alarms: Logical OR or AND of alarms to an individual hardware output is available.

Display
Digital Display: Dual 7 segment LED;
Top: .36” high, Bottom .28” high.
Status Indicators: Individual LED indictors for OUT, Exceed, ALM, and when in Setup

Program / Profile Specifications
Programs: Four with 16 free form steps each
Length of Program: 16 steps per program
Step Types: Ramp, dwell (soak), or end
Program Cycling: 1 to 9999 cycles, or infinite
Delayed Start: 0 to 99:59 hours:minutes or minutes seconds, depending on the time base selected.
Control: Start, Run, Hold and Abort from keypad if remote run/hold is not used. Remote start, run, and hold if the option is turned on.
Start From: Current process value or setpoint.
At End: Controls at the last setpoint.
Guaranteed Soak: During dwells (soak) the controller can be programmed to stop advancing the dwell time while the process value is outside a specific band around setpoint. This capability can be disabled or the controller can be set to wait until instructed to "run" after the soak time has expired.
Time Base: Hours:Minutes or Minutes:Seconds
Step Time: 0 to 99:59 hours:minutes or minutes seconds, depending on the time base selected.
Ramp Rate: 0 to 9999 least significant digits per hour or minute, depending on the time base (this applies only when the program mode is set to Rate).
Event Output: Programmable to ON or OFF at the beginning of each step. Output 2 or 3 can be used as the event output.
Profile Active: Output 2 or 3 can be set to be energized or de-energized whenever a profile/program is running.
Power Loss Recovery: If power is removed and applied while a profile is running, the unit can be programmed to re-start or continue the profile.

Remote Run / Hold Input (Option)
Type: Voltage free or TTL compatible
ON - Currently selected program will run or (if currently held) resuming running.
OFF - Currently running program will be held.
Voltage Free Operation: Connection of contacts to external switch or relay; contact open = OFF (minimum contact resistance = 5000Ω), contacts closed = ON (maximum contact resistance = 50Ω)
TTL Levels: ON: -0.6V to 0.8V
OFF: 2.0V to 24V
Maximum Input Delay (OFF-ON): 1 Second
Minimum Input Delay (ON-OFF): 1 Second

Physical Dimensions
Dimensions: 1/16 DIN front panel, 110mm (4.3") deep
Front Panel Rating: NEMA 4X/IP65
Weight: 227 g. (8 oz.) maximum

Communications
Type: RS-485 serial communication port
Protocol: MODBUS/RTU

Ratings / Agency Approvals
CE, UL & cUL recognized (E67237),

Warranty
3 years