MIC 1166 1/16 DIN Microbased Profile Controller
|
Quick Specs...
- Small Size - Maximum Function
-
Programmable profile device
-
Holds up to 4 programs of 16 free-format segments
-
Stores and implements temperature control sequences including ramp/soak profiles using exclusive PID techniques.
|
|
|
|
Overview / Design Principle:
The Partlow brand MIC 1166 1/16 DIN profiler may seem small, but it packs a punch with holding up to 4 programs of 16 free-format segments each and includes an event output. The controller can be configured from the front of the instrument or by a PC through a configuration port. The configuration port has a dual purpose; first it can be used to modify the controller setups and secondly, it can be used to transfer programs or profiles.
This control has RaPID, Response Assisted PID, a fuzzy logic algorithm plus a pre-tune algorithm, that when combined provide shorter start-up times and reduced overshoot.
The Partlow brand MIC 1166 contains many of the features of larger more expensive profilers such as: guaranteed soak, delayed start, profile active output, profile recovery features, profile cycling, plus an optional digital input for remote run/hold. RS-485 communications is also available with convenient, full access to all profile data.
Modular I/O options allow for field upgrades by adding or replacing boards.
Features / Benefits:
- Dual, 4-digit, LED displays
- 1/16 DIN panel mount
- Universal Input for thermocouple, RTD, DC linear mA/V/mV user-selectable
- Up to 3 outputs; relay, 4-20mA, SSR driver, Triac
- Alarm, control, retransmit, event output functions
- PID, ON/OFF, profile (ramp/soak) control
- Optional RS-485 serial communications
- Program security
|
|
|
Applications:
Programmable profile device that stores and implements temperature control sequences including ramp/soak profiles using exclusive PID techniques.
Industries:
- Industrial and lab ovens/furnaces, plastics and thermal forming
- Form/fill and seal
- Packaging applications
- Semiconductor
- And any others where low costs, smaller size and unmatched connectivity are critical requirements.
|
|
- Dual Display for fast view of process and control parameters
- Full PID capability
- Universal input for voltage, current, thermocouple and RTD
- Profile Cycling
- Program loading via communications port
|
| Operating Temperature: |
0 to 55°C, 32 to 131°F |
| Storage Temperature: |
-20 to 80°C, -4 to 176°F |
| Humidity: |
20 to 95% RH, non condensing |
| Line Voltage: |
90 - 264VAC, 50/60 Hz |
| Power Consumption: |
4 Watts |
| Common Mode Rej.: |
120 db at 50/60 Hz |
| Series Mode Rej.: |
> 500% of span 50/60 Hz |
| Thermocouple Types : |
J, K, T, R, S, B, L and N |
| RTD: |
Three-wire PT100, DIN 43760 |
| Volts (VDC): |
0-5, 1-5, 0-10, 2-10 |
| Millivolts: |
0 - 50 mVDC, 10 - 50 mVDC |
| Milliamps: |
0 - 20 mA or 4 - 20 mA |
| Sample Rate: |
250 ms |
| Relay: |
SPDT rated at 2 amps resistive at 120/240 VAC |
| SSR Driver: |
> 4.3 VDC into 250Ω minimum |
| Triac Output: |
1 amp @ 40°C derated to 1/2 amp @ 80°C |
| Current Output: |
0 - 20 mA, 4 - 20 mA, eight bit resolution |
| Volts DC Output: |
0 - 10 V, 0 - 5 V, eight bit resolution |
| Control Types: |
RaPID, PID, PID/on-off, on-off |
| RaPID: |
Response Assisted PID is a fuzzy logic mixing / weighting of P, I, and D terms to provide dramatic performance improvements as compared to conventional PID techniques. |
| Auto Tune Types: |
Pre-Tune |
| Proportional Bands: |
0 (OFF), 0.5% - 999.9% of input scan @ 0.1% increments |
| Auto Reset: |
1s-99min 59sec and OFF |
| Rate: |
0 (OFF) - 99min 59sec |
| Manual Reset: |
Adjustable in the range 0-100% of output power (single output) or -100% to +100% of output power (dual output) |
| Deadband / Overlap: |
-20% to +20% of proportional band 1 + proportional band 2 |
| ON / OFF Hysteresis: |
0.1% to 10.0% of input span |
| Auto / Manual Control: |
User-selectable with "bumpless" transfer into and out of Manual control. |
| Cycle Times: |
Selectable for 0.5sec to 512sec in binary steps |
| Setpoint Range: |
Limited by Setpoint Upper and Setpoint Lower Limits |
| Setpoint Ramp: |
Ramp rate selectable 1-9999 LSDs per hour and infinite. Number displayed is decimal point aligned with selected range. |
| Maximum Number: |
Two "soft" alarms |
| Maximum # Outputs: |
Up to 2 outputs can be used for alarm purposes |
| Combination Alarms: |
Logical OR or AND of alarms to an individual hardware output is available. |
| Digital Display: |
Dual 7 segment LED;
Top: .36” high, Bottom .28” high. |
| Status Indicators: |
Individual LED indictors for OUT, Exceed, ALM, and when in Setup |
| Programs: |
Four with 16 free form steps each |
| Length of Program: |
16 steps per program |
| Step Types: |
Ramp, dwell (soak), or end |
| Program Cycling: |
1 to 9999 cycles, or infinite |
| Delayed Start: |
0 to 99:59 hours:minutes or minutes seconds, depending on the time base selected. |
| Control: |
Start, Run, Hold and Abort from keypad if remote run/hold is not used. Remote start, run, and hold if the option is turned on. |
| Start From: |
Current process value or setpoint. |
| At End: |
Controls at the last setpoint. |
| Guaranteed Soak: |
During dwells (soak) the controller can be programmed to stop advancing the dwell time while the process value is outside a specific band around setpoint. This capability can be disabled or the controller can be set to wait until instructed to "run" after the soak time has expired. |
| Time Base: |
Hours:Minutes or Minutes:Seconds |
| Step Time: |
0 to 99:59 hours:minutes or minutes seconds, depending on the time base selected. |
| Ramp Rate: |
0 to 9999 least significant digits per hour or minute, depending on the time base (this applies only when the program mode is set to Rate). |
| Event Output: |
Programmable to ON or OFF at the beginning of each step. Output 2 or 3 can be used as the event output. |
| Profile Active: |
Output 2 or 3 can be set to be energized or de-energized whenever a profile/program is running. |
| Power Loss Recovery: |
If power is removed and applied while a profile is running, the unit can be programmed to re-start or continue the profile. |
| Type: |
Voltage free or TTL compatible
ON - Currently selected program will run or (if currently held) resuming running.
OFF - Currently running program will be held. |
| Voltage Free Operation: |
Connection of contacts to external switch or relay; contact open = OFF (minimum contact resistance = 5000Ω), contacts closed = ON (maximum contact resistance = 50Ω) |
| TTL Levels: |
ON: -0.6V to 0.8V
OFF: 2.0V to 24V |
| Maximum Input Delay (OFF-ON): |
1 Second |
| Minimum Input Delay (ON-OFF): |
1 Second |
| Dimensions: |
1/16 DIN front panel, 110mm (4.3") deep |
| Front Panel Rating: |
NEMA 4X/IP65 |
| Weight: |
227 g. (8 oz.) maximum |
| Type: |
RS-485 serial communication port |
| Protocol: |
MODBUS/RTU |
| CE, UL & cUL recognized (E67237), |
|
|
Available Specifications: